Midea "MFJ"

Operating ambient temperatures

Cooling mode
+ 18
... + 43 °C
Heating mode
- 7
... + 24 °C

Suggested retail price

96,140-hrv.

    Blue Fin

    Blue fin heat exchanger cover - Protection against corrosion. Special anti-corrosion coating of the heat exchanger, protection from atmospheric phenomena and effects of aggressive environment. May differ in color (have blue, green, gold or no color at all (clear varnish)

    Refrigerant Leakage Detect

    Its a electronical function of Main PCB and self-diagnostic system into AC.

    When pipe-temperature sensor at inlet line of evaporator will indicate highest temperature, system will indicate "EC" code in a display of indoor units, its mean "ask for service centre for visit maintance team with leakage detectors and tools"

    Dry Mode

    Dry mode automatically selects cooling, based on the difference between fixed and temparaturoy actual room temperature. The temperature is regulated while reducing humidity repeated switching on and off of the cooling and ventilation only. when the dry mode on the remote control shows "Drop"

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    Indoor  Model MFJ2-48ARN1-R
    Power supply   V-ph-Hz 220~240,1, 50
    Cooling Capacity                      Btu/h 48000
    Input W 5128
    Current A 9
    EER W/W 2.8
    Heating Capacity                      Btu/h 51000
    Input W 4220
    Current A 7.4
    COP W/W 3.61
    Indoor air flow (Hi/Med/Lo)   m3/h  
    Indoor noise level (Hi/Lo) dB(A) 54/50
    Indoor unit Dimension (W×D×H) mm 540x410x1825
    Packing (W×D×H) mm  
    Net/Gross weight kg  
    Controller standard Wired control
    Operation temperature 17~30
    Room temperature Cooling 17~32
    Heating 0~30
    Outdoor  Model MOU-48HN1-R
    Power supply V-ph-Hz 380-415-3-50
    Max. input consumption         W 6300
    Max. input current              A 11
    Compressor Type    Scroll
    Brand    Panasonic
    Outdoor noise level (sound pressure)    dB(A) 63
    Throttle type   Capillary
    Outdoor unit Dimension(WxDxH) mm 900x350x1170
    Packing(WxDxH) mm 1032x443x1307
    Net/Gross weight   kg 93.2/105
    Refrigerant type/Quantity  Type   R410A
    Charged volume kg 3.25
    Design pressure MPa 4.2/1.5
    Refrigerant piping Liquid side/ Gas side   mm(inch)

    Φ9.52/Φ19

    (3/8" & 3/4")

    Max. pipe length    m 50
    Max. difference in level m 30