Midea "IDU of MDV cassette type MI2, 2-way Q2DHN1 series"

Suggested retail price

38,760- ... 45,600-hrv.

    Central Controller

    1. The central controller is used for centralized management of indoor units (up to 64 indoor units can be connected via an adapter card).
    2. The indoor units can be divided into 20 zones, each zone can contain no more than 64 indoor units. All indoor units in one zone can only be set to the same mode. (By default, "the zone is not assigned to indoor units").
    3. Users can select the desired mode and temperature with a weekly schedule.

    Multi-Bend Heat Exchanger

    Increased heat. This unit uses the heat exchangers with tubes of a special design, the inner surface of which has trapezoidal notches "Innergrove cooper", which provides maximum heat transfer surface area increased. Due to this heat increases by 28%, reduced power consumption, and hence increases the efficiency of the system.

    • DC fan
    • Built-in water pump
    • fresh air supply
    • Controller is optional
    Model name MI2-22Q2DHN1 MI2-28Q2DHN1 MI2-36Q2DHN1
    Power supply 1-phase, 220-240V, 50/60Hz
    Cooling1 Capacity kW 2.2 2.8 3.6
    kBtu/h 7.5 9.6 12.3
    Power input W 35 40 40
    Heating2 Capacity kW 2.6 3.2 4
    kBtu/h 8.9 10.9 13.6
    Power input W 35 40 40
    Fan motor Model ZKSP-100-8-5
    Type DC
    Brand Panasonic/Matchwell
    Speed3 r/min 640/620/580/540/510/470/420 690/680/640/600/560/510/450
    Coil Number of rows 1
    Tube pitch × row pitch mm 21×13.37
    Fin spacing mm 1.5
    Fin type Hydrophilic aluminum
    Tube OD and type mm Ф7 Inner-groove
    Dimensions (L×H ×W) mm 882×210×13.37
    Number of circuits 4
    Air flow rate3 m3/h 654/612/571/530/488/449/410 725/679/641/591/554/509/458
    Sound pressure level4 dB(A) 33/31/30/29/27/25/24 35/33/32/30/29/27/25
    Main body Net dimensions5 (WxHxD) mm 1172×299×591
    Packed dimensions
    (WxHxD)
    mm 1355×400×675
    Net/Gross weight kg 33.5/42.0
    Panel Model   MBQ2-01
    Net dimensions (W×H×D) mm 1430×53×680
    Packed dimensions
    (W×H×D)
    mm 1525×130×765
    Net/Gross weight kg 10.5/15
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model BD20FKS(L)
    Design pressure (H/L) MPa 4.4/2.6
    Pipe
    connections
    Liquid/Gas pipe mm Ф6.35/Ф12.7
    Drain pipe mm OD Ф32
    Model name MI2-45Q2DHN1 MI2-56Q2DHN1 MI2-71Q2DHN1
    Power supply 1-phase, 220-240V, 50/60Hz
    Cooling1 Capacity kW 4.5 5.6 7.1
    kBtu/h 15.4 19.1 24.2
    Power input W 50 69 98
    Heating2 Capacity kW 5 6.3 8
    kBtu/h 17.1 21.5 27.3
    Power input W 50 69 98
    Fan motor Model ZKSP-100-8-5
    Type DC
    Brand Panasonic/Matchwell
    Speed3 r/min 770/720/670/620/580/560/540 970/920/860/800/760/710/670 1120/1090/1050/1010/940/860/790
    Coil Number of rows 2
    Tube pitch × row pitch mm 21×13.37
    Fin spacing mm 1.5
    Fin type Hydrophilic aluminum
    Tube OD and type mm Ф7 Inner-groove
    Dimensions (L×H ×W) mm 882×210×26.74
    Number of circuits 6
    Air flow rate3 m3/h 850/792/731/670/631/592/550 980/925/855/800/755/702/670 1200/1115/1068/1000/921/808/770
    Sound pressure level4 dB(A) 37/36/35/34/32/31/30 39/37/36/35/33/31/30 44/42/41/40/38/36/34
    Main body Net dimensions5 (WxHxD) mm 1172×299×591
    Packed dimensions (WxHxD) mm 1355×400×675
    Net/Gross weight kg 35/43.5
    Panel Model   MBQ2-01
    Net dimensions (W×H×D) mm 1430×53×680
    Packed dimensions
    (W×H×D)
    mm 1525×130×765
    Net/Gross weight kg 10.5/15
    Refrigerant type R410A
    Throttle Type Electronic expansion valve
    Model BD20FKS(L)
    Design pressure (H/L) MPa 4.4/2.6
    Pipe
    connections
    Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.53/Ф15.9
    Drain pipe mm OD Ф32
    Notes:          
    1.     Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
    2.     Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
    3.     Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.  
    4.     Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a semi-anechoic chamber.
    5.     Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.